search

hb039 Start up surges on Constant Voltage Transformers (CVTs)

The switch on current surge for a Constant Voltage Transformer (CVT) consists of two components. One of these is fixed at about 8 times running current for 5 - 10 mSec. Superimposed on this will be a ‘spike’ which will be dependent on where in the mains cycle the transformer was last turned off and where in the cycle it is turned back on. The spike will be less than 1 mSec and varies from zero to 25 times running current if the supply is very `stiff’. The input surge current at switch on is not significantly affected by the output load condition. The surge current will be substantially proportional to applied line voltage. Our normal circuit breaker recommendation is to fit a ‘Type 4 ‘, 'TypeD' or ‘Curve 66’ (i.e. motor rated) unit which should function without nuisance tripping. Fuse earth loop impedance and cable size suggestions are shown.

Fuse ratings

Fuses known as 'motor circuit fuse links' in BS 88 / IEC629 are ideal for CVT's. The GEC type 'T' H.R.C. are used in the table and European types should be the type called `aM' or if available type `gTr'. We suggest that installers use a wall-mounting switch fuse arrangement or 'red-spot' fittings. The table shows the MINIMUM fuse that can be used in normal installations, if using a breaker the choose the next size LARGER in your breaker range. Attention must be given to special cases where input voltage limits may go below the -20% figures used in the table. Cable sizes are also the minimum recommended by GEC for use with each fuse rating. The fuses will protect a PVC cable according to rule 433-2 for 'open conditions'. Earth loop impedance is for SAFETY considerations and does not reflect the needs of a clean earth. Protection against electric shock is provided by these fuses when correctly installed. Part numbers are based on GEC published data and some so-called direct equivalents may not be suitable. Discrimination must be proven under the requirements of the current edition of the local permanent wiring regulations BS 76711992  - it remains the responsibility of the installer to ensure that the supply is protected.

Output fuses

All Advance CVT’s have automatic overload characteristics. In normal situations the output current will limit at about 2 times rated current. The output voltage will collapse to near zero dependent on the fault impedance. It is impractical to provide a fuse that will remain intact for normal full load use and definitely open under fault conditions since the CVT does not and cannot supply enough energy. We therefore recommend no output fusing be used except where other high power conductors could become connected under fault conditions to the output circuit of the CVT or the fuse required is much smaller than the output capacity of the unit. If it is essential to protect the output we have had good success with thermal circuit breakers.

115Vac systems

VA rating

Amps @88Vac

BS88 Fuse A

IEC269 Fuse

UK Holder

Cable sq mm

Earth loop Ohms

VA rating

Amps @88Vac

BS88 Fuse

IEC269 Fuse

UK Holder

Cable sq mm

Earth loop Ohms

100

1.5

5

5aM

 

1

13

5000

65

100M125

100aM

A4

16

0.45

200

2.7

10

10aM

 

1

7.7

6000

78

100M160

100aM

A4

16

0.45

250

3.4

10

10aM

 

1

4.4

7000

88

100M200

100aM

A4

25

0.45

300

3.9

13

13aM

 

1

4.4

8000

107

200M250

200aM

B2

35

0.19

400

5.0

13

13aM

 

1

4.4

10000

134

200M250

200aM

B2

35

0.19

450

5.7

13

13aM

 

1

4.4

12500

158

315M355

 

B3

50

0.11

650

8.7

13

13aM

 

1

4.4

15000

189

315M355

 

B3

50

0.11

1000

13

20M25

20aM

A1

1.5

3

20000

267

315M355

 

B3

50

0.11

1500

19

32M50

32aM

A2

4

1.8

25000

334

400M450

 

B4

70

0.096

2100

27

32M63

32aM

A2

6

1.8

33000

441

400M450

 

B4

70

0.096

3000

39

63M80

63aM

A3

6

0.86

50000

693

630M670

 

C2

95

0.054

4000

52

63M100

63aM

A3

10

0.86

             

230Vac systems

VA rating

Amps @192Vac

BS88 Fuse A

IEC269 Fuse

UK Holder

Cable sq mm

Earth loop Ohms

VA rating

Amps @192Vac

BS88 Fuse

IEC269 Fuse

UK Holder

Cable sq mm

Earth loop Ohms

100

0.7

3

3aM

 

1

13

5000

30

32M63

32aM

A2

6

1.8

200

1.3

5

5aM

 

1

13

6000

36

63M80

63aM

A3

6

0.86

250

1.6

5

5aM

 

1

13

7000

41

63M80

63aM

A3

6

0.86

300

1.8

5

5aM

 

1

13

8000

49

63M100

63aM

A3

10

0.86

400

2.3

10

10aM

 

1

7.7

10000

61

100M125

100aM

A4

16

0.45

450

2.6

10

10aM

 

1

7.7

12500

72

100M160

100aM

A4

16

0.45

650

4

10

10aM

 

1

7.7

15000

87

100M200

100aM

A4

25

0.45

1000

6

13

13aM

 

1

4.4

20000

123

200M250

200aM

B2

35

0.19

1500

9

13

13aM

 

1

4.4

25000

153

200M250

200aM

B2

35

0.19

2100

12

20M25

20aM

A1

1.5

3

33000

202

200M315

200aM

B2

35

0.19

3000

18

20M32

20aM

A1

2.5

3

50000

318

315M355

 

B3

50

0.11

4000

24

32M50

32aM

A2

4

1.8

             

400Vac systems

VA rating

Amps @332Vac

BS88 Fuse

IEC269 Fuse

UK Holder

Cable sq mm

Earth loop Ohms

VA rating

Amps @332Vac

BS88 Fuse

IEC269 Fuse

UK Holder

Cable sq mm

Earth loop Ohms

100

0.4

3A

3aM

-

1

13

5000

17

20M32

20aM

A1

2.5

3

200

0.7

3A

3aM

-

1

13

6000

21

32M50

32aM

A2

4

1.8

250

0.9

3A

3aM

-

1

13

7000

23

32M50

32aM

A2

4

1.8

300

1.0

3A

3aM

-

1

13

8000

28

32M63

32aM

A2

6

1.8

400

1.3

5A

5aM

-

1

13

10000

35

63M80

63aM

A3

6

0.86

450

1.5

5A

5aM

-

1

13

12500

42

63M100

63aM

A3

10

0.86

650

2.3

10A

10aM

-

1

7.7

15000

50

63M100

63aM

A3

10

0.86

1000

3.4

10A

10aM

-

1

7.7

20000

71

100M125

100aM

A4

16

0.45

1500

6.4

13A

13aM

-

1

4.4

25000

89

100M160

100aM

A4

25

0.45

2100

6.8

13A

13aM

-

1

4.4

33000

117

200M250

200aM

B2

35

0.19

3000

10

20M25

20aM

A1

1.5

3

50000

187

200M315

200aM

B2

35

0.19

4000

14

20M25

20aM

A1

1.5

3

             

Output protection using thermal breakers

Since the CVT is capable of developing a steady current when marginally overloaded and exhibiting an output voltage which is slightly lower than normal it is practical to protect the load wiring with a thermal breaker. The breaker should be chosen so that under all normal operating conditions it will not see it's rating. If a fault occurs causing excess current to flow then the breaker will eventually open - even if the overload is only 105-110% of the breaker rating. The breaker will open quite quickly in the event of a short circuit in the secondary load wiring.

part of the AEL technical handbook return to hb000 Handbook Index


Valid HTML 4.01 Transitional Valid CSS! Level A conformance icon, W3C-WAI Web Content Accessibility Guidelines 1.0